Caution, 17 figure 16. horizontal venting downflow furnace, Figure 17. vertical venting – Nordyne Downflow Condensing Furnace M3RL User Manual

Page 17

Advertising
background image

17

Figure 16. Horizontal Venting

Downflow Furnace

Seal/Caulk

Around Pipe

at Building

90˚ Elbow

12"

Min.

Normal Snow Level

Wall

Coupling

First Support Should be as Close to

Furnace Connection as Possible

Combustion Air

Intake Pipe

Furnace

3" x 2"
Reducer

Exhaust
Vent
PVC or
ABS pipe

Offset with
Vent for Adequate
Dimensional Clearance

3 1/2"

See Vent Table 4

Straps or Other Suitable
Supports at Minimum of

5 ft. Intervals

Upward Pitch - 1/4" Per Foot

Outlet Exhaust Vent

Top View

6"

3 9/16"

1 7/8"

Vent

Combustion
Air Intake Pipe

Figure 17. Vertical Venting

Upward Pitch
1/4" per foot

Vent

First support should be as
close to furnace as possible

Combustion Air Intake

Pipe

5'

Combustion Air
Intake Pipe

Vent

Support System

on Vertical Rise

Below Joints

5.

Avoid areas where condensate drainage
may cause problems by dropping on plant-
ers or patios, etc. Also ensure that ex-
haust gases will not impinge on windows
or building surfaces, which may be com-
promised or damaged by condensation.
Do not install the vent terminal such that
exhaust is directed into window wells,
stairwells, under decks or into alcoves or
similar recessed areas, and do not termi-
nate above any public walkways.

6.

Select the point of wall penetration where
the minimum 1/4 inch per foot of slope up
can be maintained.

!

CAUTION:

For optimal performance vent furnace
through wall which experiences the least
exposure to winter winds.

Advertising