The LCD reporting screen in the XRT1000 and above UPS’s allows much
more flexibility in communicating faults to you, and therefore has two
classes of fault messages. The first occurs when the unit is initially turned
on as explained above, and the second is if a fault is detected during
normal operation or testing.

Model XRT1000 and above error messages

LCD DISPLAY

POSSIBLE CAUSE

ACTION TO TAKE

Input AC Low

Low AC input

Verify Incoming AC

Input AC High

Input AC is too high

Verify Incoming AC

Input

Frequency Bad

Input AC frequency out of

range for unit.

Verify incoming freq. for this

model.

Over current

Excessive output current being

drawn

Verify output load matches unit.

Check fan

Fan not running

Verify nothing has gotten into fan.

Over temp

Fan or air passages blocked

Clear air passages.

Battery Bad

Battery pack is bad or

disconnected

Check battery voltage and

connections.

Hardware fault

UPS has had a hardware fault

Call for service

Output AC high

Output voltage is too high

Call for service

Output AC low

Output voltage is too low

Call for service

The Initial Error Message can be cleared by pressing any button. If the
fault is cleared, then the fault existed from a prior shutdown. If the fault is
not cleared then the fault presently exists. If the previous fault was due to
a low battery condition and the AC line returns to normal, the UPS will
automatically re-supply power to your equipment. In the XRT1000 and
above units, you may prevent the automatic return to power by setting the
Auto Restart to OFF in the Setup menu described earlier.