Remote direct communications – Rackmount Solutions XRT Series User Manual

Page 39

Advertising
background image

38

REMOTE DIRECT COMMUNICATIONS

Pin 1:

Not Used

Pin 2:

LBW

Output signal from UPS (RS232 levels)
High signal (+3 to +12 volts)= Low
Battery Warning

Pin 3: UPS Shutdown

Input signal to UPS, Shuts down
UPS (RS232 levels)
High signal (+3 to +12 volts) = UPS OFF

Pin 4: AC Fail NO.

Output signal from UPS, open
collector, High impedance = AC OK
Low impedance to ground = AC Failed

Pin 5: Ground

Common Return

Pin 6: Low Battery Warning

Output signal from UPS, open
collector
High impedance = OK
Low impedance to ground = Low

Battery Warning

Pin 7: AC Fail NC

Output signal from UPS, open
collector High impedance = AC Failed
Low impedance to ground = AC OK

Pin 8: AC Fail Logic Signal

Output signal from UPS, logic level
Logic High (+3 to +12 volts) =
AC failed
Logic Low (0 volts) = AC OK

Pin 9: Remote Shutdown

Input signal to UPS, pulled to 5
VDC through 10 K ohms
>2.4 VDC = Normal output
<0.8 VDC = Output off