Protective grille – Roberts-Gordon HE15UT User Manual

Page 13

Advertising
background image

SECTION 3: C

LEARANCES

T

O

C

OMBUSTIBLES

7 of 73

NOTE:

1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.

2. Clearances B, C and D can be reduced by 50% after 7500 mm of tubing downstream

from the burner.

3. All measurements are in millimeters.

** When installed in the first 3 m.

FIGURE 7: LINEAR & DOUBLE LINEAR, 2 FOOT DECO GRILLE, PROTECTIVE GRILLE

Model

HE1

5

S

T

HE30DL

HE20S

T

HE40DL

HE25S

T

HE50DL

HE30S

T

HE60DL

HE35S

T

HE70DL

HE40S

T

HE45S

T

HE50S

T

A

150

150

150

150

150

150

200

200

B

890

970

970

1020

1170

1220

1280

1330

C

1570

1650

1650

1780

1930

1970

2010

2080

D

890

970

970

1020

1170

1220

1280

1330

A

C

D

B

FIGURE 8: UNDERSHIELD **

Mode

l

HE

1

5

S

T

HE

30DL

HE

20S

T

HE

40DL

HE

25S

T

HE

50DL

HE

30S

T

HE

60DL

HE

35S

T

HE

70DL

HE

40S

T

HE

45S

T

HE

50S

T

A

150

150

150

150

150

150

-

-

B

990

1020

1270

1270

1370

1400

-

-

C

840

965

1120

1120

1220

1270

-

-

D

990

1020

1270

1270

1370

1400

-

-

A

C

D

B

FIGURE 9: LINEAR & DOUBLE LINEAR, VENTING

Mod

e

l

HE1

5

S

T

HE30DL

HE20S

T

HE40DL

HE25S

T

HE50DL

HE30S

T

HE60DL

HE35S

T

HE70DL

HE40S

T

HE45S

T

HE50S

T

E

1000

1000

1000

1000

1000

1000

1000

1000

F

500

500

500

500

500

500

500

500

Radiant tubes

Fan

Unvented

Vented

E

F

Advertising