11.6 Outside Combustion Air Supply

Clean air must be ducted into the burner box through the
100 mm diameter spigot on the back of the burner box.

See Page 49, Section 11.3 for recommendations on duct
length. Air duct should be as straight as possible. Consult
the manufacturer if more than 1 x 90° bend is necessary.
The fresh air duct must be self supporting.

11.6.1 Air Supply Requirements

When fresh air duct is used, follow one of these rules:

• The flue must penetrate the roof while fresh air can

penetrate any wall. (See Page 51, Figure 31).

• The flue and fresh air supply must penetrate the roof

at a minimum of 1,000 mm apart.
(See Page 51, Figure 31).

• The flue must penetrate 1,000 mm higher than the

fresh air inlet on the same wall. (See Page 51, Figure
31
).