Roberts-Gordon HE15UT User Manual

Page 15

Advertising
background image

SECTION 3: C

LEARANCES

T

O

C

OMBUSTIBLES

9 of 73

NOTE:

1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.

2. Clearances B, C and D can be reduced by 50% after 7500 mm of tubing downstream

from the burner.

3. All measurements are in millimeters.
4. Add 60 mm clearance to uncovered u-tube.

FIGURE 14: U-TUBE, OPPOSITE 45° TILT

Mo

del

HE1

5

U

HE20UT

HE25UT

HE30UT

HE35UT

HE40UT

HE45UT

HE50UT

A

200

200

200

250

250

275

300

300

B

1370

1530

1530

1630

1780

1830

1880

1930

C

1500

1650

1650

1860

1960

2040

2110

2160

D

560

560

560

560

560

560

560

560

A

C

D

B

FIGURE 15: U-TUBE, PROTECTIVE GRILLE

Model

HE1

5

UT

HE20UT

HE25UT

HE30UT

HE35UT

HE40UT

HE45UT

HE50UT

A

150

150

150

150

150

150

200

200

B

890

970

970

1020

1170

1220

1270

1380

C

1580

1730

1730

1910

1980

2050

2110

2210

D

760

940

940

1000

1090

1150

1200

1300

A

C

D

B

FIGURE 16: U-TUBE, VENTING

Model

HE1

5

UT

HE

20

UT

HE

25

UT

HE

30

UT

HE

35

UT

HE

40

UT

HE

45

UT

HE

50

UT

E

1000

1000

1000

1000

1000

1000

1000

1000

F

500

500

500

500

500

500

500

500

Radiant tubes

Fan

Unvented

Vented

E

F

Advertising