Support of Vent Stack

The weight of the vent stack or chimney must not rest

on the heater vent connection. Support must be pro-

vided in compliance with applicable codes. The vent

should also be installed to maintain proper clearances

from combustible materials. Use insulated vent pipe

spacers where the vent passes through combustible

roofs and walls.

Vent Terminal Location

1. Condensate can freeze on the vent cap. Frozen

condensate on the vent cap can result in a blocked

flue condition.

2. Give special attention to the location of the vent

termination to avoid possibility of property dam-

age or personal injury.

3. Gases may form a white vapor plume in winter.

The plume could obstruct a window view if the ter-

mination is installed near windows.

4. Prevailing winds, in combination with below-freez-

ing temperatures, can cause freezing of

condensate and water/ice build-up on buildings,

plants or roofs.

5. The bottom of the vent terminal and the air intake

shall be located at least 12 in. above grade, includ-

ing normal snow line.

23

Table K: Venting Category Requirements

NOTE: During winter months check the vent cap

and make sure no blockage occurs from build-up of

snow or ice.

6. Un-insulated single-wall metal vent pipe shall not

be used outdoors in cold climates for venting gas-

fired equipment.

7. Through-the-wall vents for Category II and IV

appliances and non-categorized condensing appli-

ances shall not terminate over public walkways or

over an area where condensate or vapor could

create a nuisance or hazard or could be detrimen-

tal to the operation of regulators, relief valves, or

other equipment. Where local experience indi-

cates that condensate is a problem with Category

I and III appliances, this provision shall also apply.

8. Locate and guard vent termination to prevent acci-

dental contact by people or pets.

9. DO NOT terminate vent in window well, stairwell,

alcove, courtyard or other recessed area.

10. DO NOT terminate above any door, window, or

gravity air intake. Condensate can freeze, causing

ice formations.

11. Locate or guard vent to prevent condensate from

damaging exterior finishes. Use a rust-resistant

sheet metal backing plate against brick or mason-

ry surfaces.

12. DO NOT extend exposed vent pipe outside of

building beyond the minimum distance required

for the vent termination. Condensate could freeze

and block the vent pipe.

U.S. Installations

Refer to the latest edition of the National Fuel Gas

Code.

Vent termination requirements are as follows:

Combustion

Air Supply

Exhaust

Configuration

Heater Venting

Category

Certified

Materials

Combustion Air

Inlet Material

From Inside Building

(Non-Direct Venting)

Vertical

Venting

I

B-Vent

Equivalent

Horizontal Through-

the-Wall Venting

III

Stainless Steel

AL29-4C

From Outside Building

(Direct Venting)

Vertical

Venting

I

B-Vent

Equivalent

Galvanized Steel

PVC

ABS

CPVC

Horizontal Through-

the-Wall Venting

III

Stainless Steel

AL29-4C