Raypak MVB 5042004 User Manual

Page 31

Advertising
background image

31

Deadband: Deadband is a band of temperature sens-

ing where no action occurs. All temperature controllers

have a deadband and the purpose is to prevent short-

cycling of the heater. The on-board temperature

controller has a deadband of 2ºF around the differen-

tial.

Differential: A heat source must be operated with a

temperature differential in order to prevent short-

cycling. The temperature differential is divided around

the “target” temperature or set-point. The Call For Heat

(CFH) contact will close in the controller when the

water temperature is below the target temperature by

1/2 of the differential setting, and will open when the

water temperature is above the target temperature by

1/2 of the differential setting. See Fig. 30.

For systems with less than 4:1 turndown, the control

should be placed in the system return, upstream of the

inlet piping to the heater, as shown in Figs. 32, 34 and

35. This placement will avoid short cycling the heat

source. Raypak recommends using a smaller differen-

tial setting when controlling the water temperature on

the return side. As a starting point, set the return differ-

ential to 10ºF and this will allow the system return

temperature to vary 5ºF above and 5ºF below the set-

point.

For systems with more than 4:1 turndown, the recom-

mended location of the system (target) sensor is in the

system supply loop, downstream of the outlet piping

from the heater. When controlling systems with more

than 4:1 turndown; set the supply side differential to

20ºF and the temperature will vary ±10ºF around the

setpoint.

In lieu of installing the target sensor in the system

return, a properly-sized buffer tank can be installed as

shown in Fig. 31. Consult factory for buffer tank sizing.

Operating Modes

Mode 1 (Not supported) – Setpoint operation using

primary piping. The heater outlet water temperature is

controlled to the boiler target setpoint.

Mode 2 – Setpoint operation using primary/secondary

piping. The control operates the heater to satisfy a

remote system sensor. The heater is turned off based

on boiler target and boiler differential (factory default

H7, P and WHP boilers). See Fig. 32.

Mode 3 – Dedicated DHW operation using UniTemp

80 piping. A call for heat is determined by the DHW

sensor and the DHW boiler target. The heater outlet

water is also controlled to the boiler target temperature

(factory default WH1 water heaters). See Fig. 33.

*

Fig. 32: Mode 2 Primary/Secondary Piping

Fig. 30: Differential Graph

Fig. 31: Buffer Tank Piping

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Advertising