Table Q: Temperature Control Default Setpoints—Boiler

Boiler (H7)

Item

Modes

Default Setting

Range

Boil Target

2

140°F

OFF, 70 to 220°F

3

160°F

OFF, 70 to 190°F

5, 7

180°F

OFF, 70 to 220°F

Boil Max

2, 5, 7, 8

200°F

OFF, 120 to 225°F

3

180°F

OFF, 120 to 190°F

Boil Min

2, 3, 5, 7

135°F

OFF, 80 to 180°F

‘Burner’ Delay

All

0:00 min

0:00 to 3:00 min

Boil Mass

All

1 (Low)

1 (Low), 2 (Med), 3 (High)

Diff

2, 3, 5, 7

Auto

Auto, 2 to 42°F

DHW Target

3

120°F

OFF, 70 to 190°F

DHW Diff

3

5°F

2 to 10°F

‘Pump’ Dly

All

3:00 min

OFF, 0:20 to 9:55 min, ON

Outdr Start

5

70°F

35 to 85°F

Outdr Design

5

-10°F

-60 to 32°F

Boil Start

5

135°F

35 to 150°F

Boil Dsgn

5

180°F

120 to 220°F

WWSD

5

70°F

35 to 100°F

Units

All

°F

°F or °C

Mode

N/A

2

2, 3, 5, 7, 8

External Input Signal

7

2 to 10 VDC

2 to 10 VDC or 0 to 10 VDC

Offset

7

0°F

-10°F to 10°F

Pool Heater (P, WHP)

Item

Modes

Default Setting

Range

Boil Target

2

78°F

OFF, 45 to 106°F

Boil Max

2

86°F

OFF, 70 to 106°F

Boil Min

2

70°F

OFF, 45 to 106°F

‘Burner’ Delay

All

0:00 min

0:00 to 3:00 min

Boil Mass

All

1 (Low)

1 (Low), 2 (Med), 3 (High)

Diff

2

1°F

1 to 3°F

‘Pump’ Dly

All

3:00 min

OFF, 0:20 to 9:55 min, ON

Units

All

°F

°F or °C

Mode

N/A

2

2

Table R: Temperature Control Default Setpoints—Pool Heater