Check Power Supply

With multi-meter at incoming power, check voltage

between:

Hot - Common (≈120 VAC)

Hot - Ground (≈120 VAC)

Common - Ground (< 1 VAC)

Attach Manometers to Measure Pressures

1. Turn off main gas valve.

2. Attach (1) 12” scale manometer to an upstream

bleedle valve on the gas supply pipe to the heater

(Measure point “A” in Fig. 48).

3. Attach (1) 24” scale manometer to the manifold

pressure tap located on the elbow downstream of

the valve (Measure point “D” in Fig. 48).

4. Attach (1) 12” scale manometer near the fan-prov-

ing switch. Pull black cap from air pressure switch

tee and connect the manometer. NOTE: Retain

caps for reinstallation later.

Check Gas Supply Pressure

1. Slowly turn on main gas shut-off valve.

2. Read the gas supply pressure from the manome-

ter; minimum supply pressure for natural gas is 4.0

in. WC, recommended supply is 7.0 in. WC, mini-

mum supply pressure for propane gas is 4.0 in.

WC, recommended supply is 11.0 in. WC (dynam-

ic readings, full fire input).

WARNING: If Common - Ground is > 1 VAC,

STOP: Contact electrician to correct ground failure.

Failure to do this may burn out 120V-24V

transformer, or may cause other safety control

damage or failure.

Start-Up

1. Turn power on.

2. Turn on the heater, wait approximately 15 seconds

after the blower starts, and the igniter should start

to glow (observable through the observation port

located at the front, bottom of the heater). Look

into the sight glass located at the bottom of the

front panel to check igniter operation. Gas valve

should open in 45-60 seconds.

3. The heater ignites at 50% of full rate (as indicated

on the LCD display of the temperature control

located in the upper right of the front panel).

4. If the burner fails to light on the first trial, it will try

for ignition up to three times before going into lock-

out with the standard ignition module. If the heater

is equipped with the optional single-try ignition

module, it will go into lockout.

5. Wait until the controller indicates 100% on the fir-

ing rate display screen (approximately 30

seconds).

Blower Check

1. Check blower suction using the manometer

attached to the fan pressure switch tee, with the

heater firing at 100% input. The reading should be

as noted in Table V for both natural and propane

gas.

2. FOR REFERENCE ONLY: Measure the blower

amp draw with the heater firing at 100% input and

compare the measured value to the values in

Table U. The amp draw is measured with a clamp-

on type amp probe clamped to the 14 AWG black

power wire going into the blower.

3. When firing at 100%, the desired heater combus-

tion CO2 is between 8.5 and 9.0% for natural gas

and 9.5 and 10.0% for propane with CO less than

100 ppm. If this combustion cannot be achieved

GAS

TO BURNER

A

B

C

D

Fig. 48: Gas Pressure Measurement Locations

3. If the gas pressure is greater than 14.0 in. WC,

turn off the main gas shut-off valve, upstream of

the heater.

NOTE: The values in Tables V, W and X represent

the conditions when the heater is at full firing rate at

sea level.

NOTE: Pressure and combustion data are provided

with the heater.