RuggedCom RX1512 User Manual

Page 44

Advertising
background image

Chapter 5

EMI And Environmental Type Tests

RUGGEDCOM RX1512

Installation Guide

38

Table: IEEE 1613 (C37.90.x) EMI Immunity Type Tests

b

Test

Description

Test Levels

Enclosure Contact

+/-2kV, +/-4kV, +/- 8kV

IEEE C37.90.3

ESD

Enclosure Air

+/-4kV, +/-8kV, +/-15kV

IEEE C37.90.2

Radiated RFI

Enclosure ports

35 V/m

Signal ports

+/- 4kV @ 2.5kHz

D.C. Power ports

+/- 4kV

IEEE C37.90.1

Fast Transient

Earth ground ports

+/- 4kV

Signal ports

2.5kV common mode @1MHz

IEEE C37.90.1

Oscillatory

D.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

Signal ports

5kV (Fail-Safe Relay output)

IEEE C37.90

H.V. Impulse

D.C. Power ports

5kV

Signal ports

2kVAC

IEEE C37.90

Dielectric Strength

D.C. Power ports

2kVDC

b

Meets Class 2 requirements for an all-fiber configuration. Meets Class 1 requirements for copper ports.

Table: Environmental Type Tests

Test

Description

Test Levels

IEC 60068-2-1

Cold Temperature

Test Ad

-40°C, 16 Hours

IEC 60068-2-2

Dry Heat

Test Bd

+85°C, 16 Hours

IEC 60068-2-30

Humidity (Damp Heat, Cyclic)

Test Db

95% (non-condensing), 55°C , 6 cycles

IEC 60255-21-1

Vibration

2g @ (10 - 150) Hz

IEC 60255-21-2

Shock

30g @ 11mS

Advertising