Protection on twisted-pair data ports, Micro-d 10/100basetx port pin configuration – RuggedCom M2100 User Manual

Page 18

Advertising
background image

2. Installation

RuggedCom® RuggedSwitch®

18

M2100 Installation Guide Rev 1.0

Figure 2.13. Micro-D 10/100BaseTX

Port Pin Configuration

Pin

Signal

1

TX+

2

No Connection

3

No Connection

4

No Connection

5

RX+

6

TX-

7

No Connection

8

No Connection

9

RX-

Table 2.3. Micro-D 10/100BaseTX Port Pin
Assignment

Figure 2.14. Micro-D 10/100/1000BaseTX

Port Pin Configuration

Pin

Signal

1

TP1+ (B+)

2

TP3+ (D+)

3

No Connection

4

TP2+ (C+)

5

TP0+ (A+)

6

TP1- (B-)

7

TP3- (D-)

8

TP2- (C-)

9

TP0- (A-)

Table 2.4. Micro-D 10/100/1000BaseTX Port Pin
Assignment

• For 10/100Base-TX ports: Pin 2 and Pin 7 are internally connected; Pin 4 and Pin 8 are

internally connected on the PCB board.

• For 10/100/1000Base-TX ports: Pin 3 and Pin 8 are internally connected on the PCB

board.

2.6.2. Protection on Twisted-Pair Data Ports

RuggedCom does not recommend the use of CAT-5 cabling of any length for critical real-time substation
automation applications. However, transient suppression circuitry is present on all copper ports to
protect against damage from electrical transients and to ensure IEC 61850-3 and IEEE 1613 Class 1
conformance. This means that during the transient event communications errors or interruptions may
occur but recovery is automatic.