4. Type Tests

RuggedCom® RuggedSwitch®

24

M2100 Installation Guide Rev 1.0

4. Type Tests

4.1. IEC 61850-3 Type Tests

Test

Description

Test Levels

Severity

Levels

Enclosure Contact

± 8 kV

4

IEC 61000-4-2

ESD

Enclosure Air

± 15 kV

4

IEC 61000-4-3

Radiated RFI

Enclosure Ports

20 V/m

X

Signal ports

± 4 kV @ 2.5kHz

X

DC Power ports

± 4 kV

4

AC Power ports

± 4 kV

4

IEC 61000-4-4

Burst (Fast

Transient)

Earth ground ports

± 4 kV

4

Signal ports

± 4 kV line-to-earth, ± 2 kV line-to-line

4

DC Power ports

± 2 kV line-to-earth, ± 1 kV line-to-line

3

IEC 61000-4-5

Surge

AC Power ports

± 4 kV line-to-earth, ± 2 kV line-to-line

4

Signal ports

10 V

3

DC Power ports

10 V

3

AC Power ports

10 V

3

IEC 61000-4-6

Induced

(Conducted) RFI

Earth ground ports

10 V

3

IEC 61000-4-8

Magnetic Field

Enclosure Ports

40 A/m, continuous, 1000 A/m for 1 s

N/A

DC Power ports

30% for 0.1 s, 60% for

0.1 s, 100% for 0.05 s

N/A

IEC 61000-4-29

Voltage Dips

& Interrupts

AC Power ports

30% for 1 period, 60% for 50 periods

N/A

IEC 61000-4-11

Voltage Dips

& Interrupts

AC Power ports

100% for 5 periods, 100% for 50 periods

N/A

Signal ports

2.5 kV common, 1 kV diff. mode @ 1 MHz

3

DC Power ports

2.5 kV common, 1 kV diff. mode@1MHz

3

IEC 61000-4-12

Damped Oscillatory

AC Power ports

2.5 kV common, 1 kV diff. mode @ 1 MHz

3

Signal ports

30 V Continuous, 300 V for 1 s

4

IEC 61000-4-16

Mains Frequency

Voltage

DC Power ports

30 V Continuous, 300 V for 1 s

4

IEC 61000-4-17

Ripple on DC

Power Supply

DC Power ports

10%

3

Signal ports

2 kVAC (Fail-Safe Relay output)

N/A

IEC 60255-5

Dielectric Strength

DC Power ports

1.5 kVDC

N/A