Ieee 1613 type tests, Military standard tests, 25 4.3. military standard tests – RuggedCom M2100 User Manual

Page 25

Advertising
background image

4. Type Tests

RuggedCom® RuggedSwitch®

25

M2100 Installation Guide Rev 1.0

Test

Description

Test Levels

Severity

Levels

AC Power ports

2 kVAC

N/A

Signal ports

5 kV (Fail-Safe Relay output)

N/A

DC Power ports

5 kV

N/A

IEC 60255-5

H.V. Impulse

AC Power ports

5 kV

N/A

Table 4.1. IEC 61850-3 Type Tests

4.2. IEEE 1613 Type Tests

Test

Description

Test Levels

Enclosure Contact

± 8 kV

IEEE C37.90.3

ESD

Enclosure Air

± 15 kV

IEEE C37.90.2

Radiated RFI

Enclosure ports

35 V/m

Signal ports

± 4 kV @ 2.5 kHz

DC Power ports

± 4 kV

AC Power ports

± 4 kV

IEEE C37.90.1

Fast Transient

Earth ground ports

± 4 kV

Signal ports

2.5 kV common mode @ 1 MHz

DC Power ports

2.5 kV common, 1 kV

diff. mode @ 1 MHz

IEEE C37.90.1

Oscillatory

AC Power ports

2.5 kV common, 1 kV

diff. mode @ 1 MHz

Signal ports

5 kV (Fail-Safe Relay output)

DC Power ports

5 kV

IEEE C37.90

H.V. Impulse

AC Power ports

5 kV

Signal ports

2 kVAC

DC Power ports

1.5 kVDC

IEEE C37.90

Dielectric Strength

AC Power ports

2 kVAC

Table 4.2. IEEE 1613 Type Tests

4.3. Military Standard Tests

Test

Description

Test Levels

MIL-STD-901D

Shock (Hard-Mounted)

Grade A, Equipment Class

I, Shock Type A Equipment

MIL-STD-167-1

Vibration

Type I (Upper Frequency of 33 Hz)