Irig-b connection considerations, Ethernet ports, Copper ports – RuggedCom RS416 User Manual

Page 32: Table 12: irig-b daughter board led, 5 ethernet ports, 2 irig-b connection considerations, 1 copper ports

Advertising
background image

Ethernet Ports

32

RuggedCom

®

RuggedServer™ RS416 Family Installation Guide rev118

Figure 24 shows layout of the BNC connectors on the IRIG-B I/O board. The LED in the
center of the board, indicated by the mark, reflects the status of the received IRIG-B
signal, and is described in Table 12.

Figure 24: IRIG-B daughter board BNC connections

LED Color

Meaning

Off

No IRIG-B signal detected

Red

Errors detected in received

IRIG-B signal

Green

Received IRIG-B signal is good

Table 12: IRIG-B Daughter Board LED

4.2 IRIG-B Connection Considerations

The number of IRIG-B devices that can be connected to a given IRIG-B output is
dependent on the cabling type and length as well as the input impedances of connected
devices. Figure 25 shows a simplified circuit diagram of the interface between an IRIG-B
output and connected devices.

Vs

Rs

Rc

R

L

/N

Source

Cabling

Device

Figure 25: IRIG-B Output Simplified Schematic

The maximum number of devices (N) that can be connected to the source is determined
by verifying that the source current (I

S

) required to drive the connected devices is less

than the maximum drive current the output can provide, and that the load voltage (V

L

)

seen by the connected devices is greater than their minimum required voltage. Refer to
section 6.3.2 for IRIG-B port specifications.

5 Ethernet Ports

5.1 Copper Ports

The RS416 may have up to 4 10/100BaseTX ports that allow connection to standard
CAT-5 UTP cable with RJ45 male connectors. All RJ45 Ethernet ports feature auto-