Ieee 1613 type tests, Iec environmental type tests, Agency approvals – RuggedCom RS416 User Manual

Page 42: 3 iec environmental type tests

Advertising
background image

Type Tests

42

RuggedCom

®

RuggedServer™ RS416 Family Installation Guide rev118

7.2 IEEE 1613 Type Tests

IEEE Test

IEEE
1613

Clause

Description

Test Levels

C37.90.3

9

ESD

Enclosure Contact

+/- 8kV

Enclosure Air

+/- 15kV

C37.90.2

8

Radiated RFI

Enclosure ports

35 V/m

C37.90.1

7

Fast Transient

Signal ports

+/- 4kV @ 2.5kHz

D.C. Power ports

+/- 4kV

A.C. Power ports

+/- 4kV

Earth ground ports

+/- 4kV

C37.90.1

7

Oscillatory

Signal ports

2.5kV common mode @ 1MHz

D.C. Power ports

2.5kV common & differential mode @ 1MHz

A.C. Power ports

2.5kV common & differential mode @ 1MHz

C37.90

6

H.V. Impulse

Signal ports

5 kV (Failsafe Relay)

D.C. Power ports

5 kV

A.C. Power ports

5 kV

C37.90

6

Dielectric

Strength

Signal ports

2kVAC

D.C. Power ports

1.5kVDC

A.C. Power ports

2kVAC

Table 25 - IEEE 1613 Type Tests

Notes:

If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (During
disturbance, errors may occur but recovery is automatic).

If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (During
disturbance, no errors will occur).

7.3 IEC Environmental Type Tests

Test

Description

Test Levels

Severity

Levels

IEC 60068-2-1

Cold

Temperature

Test Ad

-40 deg. C, 16 Hours

N/A

IEC 60068-2-2

Dry Heat

Test Bd

+85 deg. C, 16 Hours

N/A

IEC 60068-2-30

Humidity (Damp

Heat, Cyclic)

Test Db

95% (non-condensing), 55°C, 6

cycles

N/A

IEC 60255-21-1

Vibration

2g @ (10-150) Hz

Class 2

IEC 60255-21-2

Shock

30g @ 11 ms

Class 2

Table 26 - Environmental Type Tests