7 Type Tests

7.1 IEC 61850-3 Type Tests

Test

Description

Test Levels

Severity

Levels

IEC 61000-4-2

ESD

Enclosure Contact

+/- 8kV

4

Enclosure Air

+/- 15kV

4

IEC 61000-4-3

Radiated RFI

Enclosure ports

20 V/m

Note 1

IEC 61000-4-4

Burst (Fast

Transient)

Signal ports

+/- 4kV @ 2.5kHz

Note 1

D.C. Power ports

+/- 4kV

4

A.C. Power ports

+/- 4kV

4

Earth ground ports

+/- 4kV

4

IEC 61000-4-5

Surge

Signal ports

+/- 4kV line-to-earth, +/- 2kV line-to-

line

4

D.C. Power ports

+/- 2kV line-to-earth, +/- 1kV line-to-

line

3

A.C. Power ports

+/- 4kV line-to-earth, +/- 2kV line-to-

line

4

IEC 61000-4-6

Induced

(Conducted)

RFI

Signal ports

10V

3

D.C Power ports

10V

3

A.C. Power ports

10V

3

Earth ground ports

10V

3

IEC 61000-4-8

Magnetic

Field

Enclosure ports

40 A/m continuous, 1000 A/m for 1 s

Note 1

1000 A/m for 1 s

5

IEC 61000-4-29

Voltage Dips

& Interrupts

D.C. Power ports

30% for 0.1s, 60% for 0.1s, 100% for

0.05s

N/A

A.C. Power ports

30% for 1 period, 60% for 50 periods

N/A

IEC 61000-4-11

100% for 5 periods, 100% for 50

periods

2

N/A

IEC 61000-4-12

Damped

Oscillatory

Signal ports

2.5kV common, 1kV differential mode

@ 1MHz

3

D.C. Power ports

2.5kV common, 1kV differential mode

@ 1MHz

3

A.C. Power ports

2.5kV common, 1kV differential mode

@ 1MHz

3

IEC 61000-4-16

Mains

Frequency

Voltage

Signal ports

30V Continuous, 300V for 1s

4

D.C. Power ports

30V Continuous, 300V for 1s

4

IEC 61000-4-17

Ripple on

D.C. Power

Supply

D.C. Power ports

10%

3

IEC 60255-5

Dielectric

Strength

Signal ports

2kV AC (Fail-Safe Relay output)

N/A

D.C. Power ports

1.5kVDC

N/A

A.C. Power ports

2kVAC

N/A

IEC 60255-5

H.V. Impulse

Signal ports

5kV (Fail-Safe Relay output)

N/A

D.C. Power ports

5kV

N/A

A.C. Power ports

5kV

N/A

Table 24 - IEC 61850-3 Type Tests

Note 1: Ruggedcom specified severity levels