Installation, Flueing arrangements - horizontal terminations, Co axial flue system (flex) (lpg & ng) – Regency Wraps P36-LPG4 User Manual

Page 14

Advertising
background image

Regency

®

P36-4 Gas Log Fireplace

14

FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS

SIMPSON DURA-VENT DIRECT FLUE GS SYSTEM and

REGENCY

®

CO AXIAL FLUE SYSTEM (FLEX)

(LPG & NG)

The diagram below shows examples of horizontal termination arrangements using two 90

o

elbows (two 45

o

elbows equal one 90

o

elbow).

Note: 1)

A

maximum

of

two

90

o

elbows are permitted.

2) A minimum of 6 ft. (1.8m) vertical from base of unit is required if two 90

o

elbows are used.

3) Minimum distance between elbows is 2 ft. (0.6m).

4) Determine the permitted range of horizontal termination arrangements by using chart in section "Simpson Dura-vent

Flueing." and deducting 3 ft. (0.9m) from the maximum horizontal distance for the second 90

o

elbow.

Simpson Dura-Vent
4" inner diameter
6-5/8" outer diameter

• Maintain clearances to combustibles as listed in section "Clearances."

• Horizontal fl ue must be supported every 3 feet (0.9 meters).

• Firestops are required at each fl oor level and whenever passing through a wall.

A fl ue guard should be used whenever the
termination is lower than the specifi ed minimum
or as per local codes.

If length "B" is increased, length "A" must be
decreased by a corresponding amount.

INSTALLATION