P36-4 Gas Log Fireplace

16

The P36 is approved for a 37 ft. (11.3m) straight vertical, with Simpson
Dura-Vent Co Axial Flue GS
fl ue systems for LPG and NG, as per the
diagram 3.

The shaded area in the diagram 3 shows all allowable combinations of
straight vertical and offset to vertical terminations with Simpson Dura-
Vent Co Axial Flue GS
fl ue systems for LPG and NG. Maximum two
45

o

elbows allowed.

• Flue must be supported at offsets
• Firestops are required at each fl oor level and whenever passing

through a wall.

• Maintain clearances to combustibles as listed in section

"Clearances."

Diagram 3

INSTALLATION