Figure 2: Installation Clearances and Clearances to Combustibles

WARNING

Fire Hazard

Some objects will catch fire or explode when placed

close to heater.
Keep all flammable objects, liquids and vapours the

required distance away from the heater.
Failure to follow these instructions can result in death,

injury or property damage.

Clearances to Combustibles

Alternative

Wall

Terminal

Roof Terminal

Air

Intake

Flue

15 cm

2.5 - 3.5 m*

3 m

60 cm

Installation Clearances

Customers

Suitable

Condenser

Unit

Insulated

Refrigerant pipes

to cooling coil

by Customer

Condense

Drain

Install to

suitable drain,

See Page 3,

Figure 1.

Air Flow

50 cm

50 cm**

30 cm

15 cm

If installed at low levels where individuals can come in contact with hot heat exchanger components,
adequate guarding must be provided.

All distances are minimum clearance requirements for service access, air flow and safety.

Free blowing DualAir

®

units must always be installed at least 1.8 m above the floor.

Ducted installations may be floor mounted.
The flue pipe must have clearance from combustibles by 5 cm.

**80 cm is necessary to
service heater.

* Free blowing DualAir

®

units may be mounted at

a higher level if destratification fans and/or turn
down nozzles are installed.