16.4 Flue Fan

IT IS IMPORTANT THAT ONLY THE CORRECT FLUE FAN SPECIFIED FOR EACH MODEL TYPE IS
USED WHEN REPLACING THESE ITEMS.

Carry out a commission after working on or changing a flue fan.

See Page 25, Section 12.

Vent Box

Outlet

Gasket

Flue Fan

Vent Box

screws

Flue

Adapter

Flue Adapter

to Flue Fan

screws

Rear Panel

Hole

Disconnect

electrical connections

at plug in tabs.

Mounting Plate

to Vent Box

screws

Mounting

Plate

Gasket

Air Plate

Mounting Plate

to Flue Fan

screws

Vent Box

Gasket

Remove screws securing outlet
flange to the flue adapter.

Remove screws securing flue
fan mounting plate to vent box
Remove screws securing
mounting plate to fan.
Refit in reverse.
Use new gaskets.
Ensure sealed joints.
Ensure mounting plate orifice is
clear and not obstructed.

MODEL

75

90

100

115

Flue Fan

AO Smith

JFIG07INS

AO Smith

JFIG07INS

AO Smith

JFIG07INS

Torin DSF

146-052

077274

RG P/N

90710001

90710001

90710001

90710450

Air mm dia

97.0

103.6

110.5

152.4

Plate in dia

3.82

4.08

4.35

6

RG P/N

11011134

11011133

11011132

11011131