30

SECTION 15: TROUBLESHOOTING

15.1 General

WARNING

Explosion Hazard

Installation must be done by a registered installer/

contractor qualified in the installation and service of

gas-fired heating equipment or your gas supplier.

Failure to follow these instructions can result in death,

injury or property damage.

If problems persist, contact

ROBERTS GORDON

®

at

Tel: +44 (0)1902 498733

or www.rg-inc.com

Heater Operating

TROUBLESHOOT ENDS. No

Adjust or replace

as necessary.

Is combination fan/limit

thermostat set correctly?

See sections 5.3 &11.3.

No

Use 15.2 to test burner.

Replace combination

fan/limit thermostat.

See sections 5.3 & 11.3 to

check combination

fan/limit thermostat settings.

Does the fan run?

No

Has burner “Locked Out”?

Yes

No

With external controls on,

does the burner continue

through the heating cycle?

No

Yes

Press the white button on

the combination fan/limit

thermostat. Does the

fan run now?

Yes

No

Does the fan run?

No

Use 15.5 to test fan.

Yes

Yes

Use 15.2 to test burner.

Is Red lockout

warning light on?

Yes

No

Turn on supplies.

Are gas & electrical

supplies on?

No

Yes

Start

Yes

For your safety and optimum heater performance use only ROBERTS GORDON

®

replacement parts.

Conduct Commissioning procedure as shown

on Page 21, Section 11