Roberts Gorden DAT100 User Manual

Page 48

Advertising
background image

D

UAL

A

IR

®

H

EATING

AND

COOLING

U

NITS

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

42

16.8.1 Fan Removal and Replacement

1. Remove motor leaving the pulley in place.

See Page 41, Section 16.8.

2. Remove screws securing the fan outlet flange

to the fan panel. (captive nuts)

3. Remove nuts and bolts securing the fan feet to

the mounting brackets.

4. Slide the fan out.

(fan is heavy, may need two people)

5. Remove the fan mounting brackets from the

fan. Retain components to fit to new fan.

6. Remove the Fan pulley by using a hexagonal

key to remove the taper lock screws. Use one
of these screws to fit into the centre jacking
screw and tighten into this position to separate
the taper lock bush and the pulley.

7. Refit the components above to the new fan and

refit in reverse order.

8. Check belt alignment and tension.

9. Check fan rotation is correct.

16.9 Combination Fan/Limit Thermostat

16.9.1 Removal and Replacement

1. Remove wires.

2. Remove the mounting screws.

3. Fit a new thermostat ensuring that the correct

temperature setting and type are selected.

See

Page 7, Section 4.3 through Page 8, Figure 4.4.

4. Reconnect wires and test operation.

Mounting Rail

Fan Foot

Screws

Fan Mounting

Brackets

(re-use on new fan)

Fan Outlet Flange

Securing Screws

Fan Plate

Bracket Screws

(re-use on new fan)

Description

Part Number

Torin Fan DDC 270-270

A047

Torin Fan DDC 241-241

A049

Advertising