Quadra-Fire • Topaz • 7009-113 Rev. N • 5/13

Figure 4.4

V

= VENT TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

A

= 12 inches ............. clearances above grade, veran-

da, porch, deck or balcony

B

= 12 inches ............ clearances to window or door

that may be opened, or to per-
manently closed window. (Glass)

D*

= 18 inches ............. vertical clearance to unventilat-

ed soffit or to ventilated soffit lo-
cated above the terminal

*30 inches ............ for vinyl clad soffits and below

electrical service

F

=

9 inches .............. clearance to outside corner

G

= 6 inches ............... clearance to inside corner

H

= 3 ft. (Canada) ...... not to be installed above a gas

meter/regulatorassembly within 3
feet (90cm) horizontally from the
center-line of the regulator

I

= 3 ft. ....................... clearance to gas service regula-

tor vent outlet

J

= 9 inches (U.S.A.)

12 inches (Canada)clearance to non-mechanical air

supply inlet to building or the
combustion air inlet to any other
appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) ......... clearance to a mechanical

(powered) air supply inlet

L** = 7 ft. ......................... clearance above paved

sidewalk or a paved driveway
located on

public property

M*** = 18 inches .............. clearance under veranda ,

porch, deck, balcony or over-
hang

42 inches .............. vinyl

** a vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings and
serves both dwellings.

*** only permitted if veranda, porch, deck or balcony is fully open on

a minimum of 2 sides beneath the floor, or meets Note 2.

(See Note 1)

(See Note 1)

S =

6 inches ................. clearance from sides of

electrical service

T = 12 inches ................ clearance above electrical

service

(See Note 3)

(See Note 3)

___________________________________________________________________

_

___________________________________________________________________

_

___________________________________________________________________

_

_

Q

MIN

R

MAX

1 cap

3 feet

2 x Q

ACTUA L

2 caps

6 feet

1 x Q

ACTUA L

3 caps

9 feet

2/3 x Q

ACTUA L

4 caps

12 feet

1/2 x Q

ACTUA L

Q

MIN

= # termination caps x 3

R

MAX

= (2 / # termination caps) x Q

ACTUAL

N

= 6 inches ................. non-vinyl sidewalls

12 inches ............... vinyl sidewalls

P

= 8 ft.

Alcove Applications

NOTE 1: On private property where termination is less than 7 feet above
a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed
cap is suggested. (See vents components pages.)

NOTE 2: Termination in an alcove space (spaces only open on one side
and without an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits.

1. There must be at least 3 feet

minimum between termination caps.

2. All mechanical air intakes within

10 feet of a termination cap must be a minimum of 3 feet below the
termination cap.

3. All gravity air intakes within 3 feet of a termination cap

must be a minimum of 1 foot below the termination cap.

NOTE 3: Location of the vent termination must not interfere with access
to the electrical service.

NOTE:

Local codes or regulations may require different

clearances.

NOTE: Termination caps may be hot. Consider their proximity to
doors or other traffic areas.

WARNING: In the U.S.: Vent system termination is NOT permitted
in screened porches.

You must follow side wall, overhang and

ground clearances as slated in the instructions.

In Canada: Vent system termination is NOT permitted in screened
porches. Vent system termination is permitted in porch areas with
two or more sides open. You must follow side wall, overhang and
ground clearances as stated in the instructions.

Quadra-Fire assumes no responsibility for the improper perfor-
mance of the appliance when the venting system does not meet
these requirements.

(See Note 2)

Electrical

Service

V

S

V

S

V

T

D*

V

D

E

B

L

v

v

v

v

v

v

v

v

B

B

A

H

M

X

J or K

I

A

G

F

U.S.

(3 FT)

B

M

N

P

R

Q

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH
VINYL SIDING, IT IS SUGGESTED THAT A VINYL PRO-
TECTOR KIT BE INSTALLED.