2.2.8 Setting the Discrete (ZONE) Display

(See Section 4.7.1 of the instruction manual for the VR200.)

Format: SZp1, p2, p3

p1:

Channel number (CC)

p2:

Lower display boundary value (0 to 95)

p3:

Upper display boundary value (5 to 100)

Example: SZ02, 30,50

This example results in the display for 0 to 100% of channel 2 in the band
from 30 to 50% of the scale.

Note

• The display bandwidth cannot be set to 5% or less.
• The lower display boundary must be less than the upper boundary.

2.2.9 Setting the Partial Expanded Display

(See Section 4.7.2 of the instruction manual for the VR200.)

Format: SPp1, p2, p3, p4

p1:

Channel number (CC)

p2:

Partial expanded display ON/OFF

p3:

Percentage of the full display span which will be compressed (1 to
99%)

p4:

Boundary value (lower display span + 1 to upper display span – 1).
Enter a numeric value excluding the decimal point.

Note

The decimal point position depends on the range (or scaling) setting. See also the input range table on Page 2-3.

Example: SP01, ON, 25, 0000

This example results in partial expanded display for channel 1 where the
value at 25% of the display scale corresponds with 0.000V.

2.2.10 Setting the Scale Value Indication On/Off (DISP_SCALE, only for VR200

with style number 1 or lower)

(See Section 4.7.3 of the instruction manual for the VR200.)

Format: SKp1, p2

p1:

Channel number (CC)

p2:

Whether to display the scale values.
Enter “ON” or “OFF”.

2.2.11 Setting the Tag

(See Section 4.7.4 of the instruction manual for the VR200.)

Format: STp1, p2

p1:

Channel number (CC) for which you want to set a tag number

p2:

Tag number (up to 7 characters)

Example: ST01, TAG1

This example sets the tag of channel 1 to “TAG1.”