Cdtx-90-2 calibrate menu – Omega CDTX-90 User Manual

Page 12

Advertising
background image

page 10

Cell

Constant:

Standard >

Cell:

Standard

1 >

Cell: Custom

1.0000 >

Cond Units:

μS >

PPM Factor:

2.00 >

Set:

Temperature >

Set:

Conductivity >

Loop Source:

Cond >

Loop Range: μS

0.0000

→ 100.000

>

Relay1 Source:

Cond >

Relay1 Mode:

Low >

Relay1

Setpnt:

10.0000

μS >

Relay1 Hys: μS

0.5000 >

Relay1 Rng: μS

10.0000

→ 40.0000

>

Relay1 PlsRate:

120 Pulses/Min

>

Last

CAL:

04-20-07 >

Select CUSTOM only if you are connecting a certifi ed conductivity sensor. Select

STANDARD for all other systems.

For STANDARD sensors: Select from these options: 0.01, 0.1, 1.0, 10.0 or 20.0.

For CUSTOM sensors: Enter the precise cell constant from the certifi cate provided with

your sensor, or from the information label on the sensor.

Select from these options: μS, mS, kΩ, MΩ,

PPM

If the Units selection is PPM, set the ratio of Total Dissolved Solids to μS. The maximum

allowable is 3 μS = 1 PPM. The TDS factor can only be set in PPM.

Adjust the temperature of the system based on an accurate external reference.

When using a h STANDARD sensor perform this single-point wet calibration for best

accuracy. Not required for CUSTOM sensors except for periodic calibration checks.

Select the input (Conductivity or Temperature) source to be associated with the current loop

output:

Select the minimum and maximum values for the current loop output.

Be sure to modify this setting if you change the Cond. Units.

Select the source (Conductivity or Temperature) for this relay output:

Select the mode of operation for the relay.

Options available are High, Low or proportional Pulse.

The relay may be disabled (Off) if not in use.

In Low or High Mode, the relay will be activated when the process reaches this value. Be

sure to modify this setting if you change the Cond. Units.

The relay will be deactivated at Setpoint ± Hysteresis, depending on High or Low Setpoint

selection.

In Pulse mode, set the process values where the proportional pulse will start and where it

will reach the maximum rate. Be sure to modify this setting if you change the Cond. Units.

In Pulse mode, set the maximum rate for the proportional Pulse. The transmitter will

accept any value from 0 to 400.

Use this “note pad” to record important dates, such as annual recertifi cation or scheduled

maintenance.

CDTX-90-2 Calibrate Menu

Display

(Factory settings shown)

Description