Cdtx-90-1 system power/loop connections – Omega CDTX-90 User Manual

Page 5

Advertising
background image

page 3

CDTX-90-1 System Power/Loop Connections

Stand-alone application, no current loop used

Transmitter

4
3
2
1

Sys. Pwr.

Loop -
Sys. Pwr.

Loop +
AUX

Power -
AUX

Power +

Power Supply
DC 12 - 24 V

Power

Supply
Power

Supply

Connection to a PLC with built-in power supply

PLC

Power Supply

Ground

Power

Supply

Loop Input

4-20 mA

Loop Input

4-20 mA

Internal PLC

Connection

Connection to a PLC/Recorder, separate supply

PLC or Recorder

Loop Input

4-20 mA in
Loop Input

4-20 mA in

DC 12 - 24 V

Power

Supply
Power

Supply

Example: Two transmitters connected to PLC/Recorder

with separate power supply

Transmitter 2

4
3
2
1

DC 12 - 24 V

Power

Supply
Power

Supply

Transmitter 1

4
3
2
1

Transmitter

4
3
2
1

Sys. Pwr.

Loop -
Sys. Pwr.

Loop +
AUX

Power -
AUX

Power +

Transmitter

4
3
2
1

Sys. Pwr.

Loop -
Sys. Pwr.

Loop +
AUX

Power -
AUX

Power +

Sys. Pwr.

Loop -
Sys. Pwr.

Loop +
AUX

Power -
AUX

Power +

Sys. Pwr.

Loop -
Sys. Pwr.

Loop +
AUX

Power -
AUX

Power +

PLC or Recorder

Channel 1

4-20 mA in

Channel 1

4-20 mA in

Channel 2

4-20 mA in

Channel 2

4-20 mA in

Terminals

Terminals

Terminals

Terminals

-

+

-

+

-

+

-

+

-

+

-

+

-

+

AUX power required for all CDTX-90 systems.

CDTX-90-1 Terminal connections

Output -

Output +

System Pwr
Loop -

System Pwr
Loop +

4

3

2

1

6

5

Sensr Gnd
(SHIELD)

Iso. Gnd
(BLACK)

Temp. IN
(WHITE)

Signal IN
(RED)

10

9

8

7

AUX
Power -

AUX
Power +

Terminals 5-6: Open-collector Output
• A transistor output, programmable (see CALIBRATE menu) as High or Low setpoint with

adjustable hysteresis and proportional pulse (to 400 pulses per minute maximum).

• May be disabled (Off) if not used.

Terminals 3 and 4: Loop Power
12-24 VDC ±10% system power
and current loop output.
Max. loop impedance:
50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24 V

Internal open-collector

output circuit

Output --

Output +

Isolation

15

W

S

D

Terminals 1-2: Auxiliary power
Provides DC power to measurement
circuit. Required for all CDTX-90
systems.

Terminals 7-10: Sensor input
7 is conductivity input
8 is temperature input
9 is the isolated signal ground
10 is the sensor earth ground