Stand-alone application, no current loop used, Connection to a plc with internal power supply – Omega CDTX-90 User Manual

Page 7

Advertising
background image

page 5

Sensr Gnd

(SHIELD)

Iso. Gnd

(BLACK)

Temp. IN

(WHITE)

Signal IN

(RED)

14

13

12

11

Output 2-

Output 2+

Output 1-

Output 1+

10

9

8

7

Loop 2-

Loop 2+

System Pwr

Loop -

System Pwr

Loop +

AUX

Power -

AUX

Power +

6

5

4

3

2

1

Terminals 7-10: Open-collector Outputs
•Two transistor outputs, programmable
as:
• High or Low setpoint with adjustable
hysteresis
• proportional pulse (to 400 pulses per
minute maximum)
• May be disabled (Off) if not used

Terminals 3-6: Loop Power
12-24 VDC ±10% system power and current loop output.
Max. loop impedance:
50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24 V

1

Internal open-collector

output circuit

Isolation

15

W

S

D

_

Terminals 1-2: Auxiliary power
Provides DC power to measurement
circuit. Required for all CDTX-90
systems.

CDTX-90-3 System Power/Loop Connections

CDTX-90-3 Terminal Connections

Terminals 11-14: Sensor input
11 is conductivity input
12 is temperature input
13 is the isolated signal ground
14 is the sensor earth ground

Trans mitte r

Terminals

P ower

S upply

12–24 V DC

+

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

6

5

4

3

2

1

NC

NC

Stand-alone application, no current loop used

Internal

PLC Connection

6

5

4

3

2

1

Trans mitte r

Terminals

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

P L C Terminals

Channel 1

4-20 mA

+

Power

Supply

12–24 VDC

Channel 2

4-20 mA

+


+

Connection to a PLC with internal power supply

Internal

PLC Connection

6

5

4

3

2

1

Trans mitte r

Terminals

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

P L C Terminals

Channel 1

4-20 mA

+

Power

Supply

12–24 VDC

Channel 2

4-20 mA

+


+

Connection to a PLC with internal power supply

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

6

5

4

3

2

1

6

5

4

3

2

1

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

Channel 3
4-20 mA in

Channel 4
4-20 mA in


+

+

Trans mitte r 1

Terminals

Trans mitte r 2

Terminals

Channel 1
4-20 mA in

Channel 2
4-20 mA in

+

+

P ower

S upply

12–24 V DC

+

Two transmitters connected to a PLC/Recorder with separate power supply

Advertising