Omega CDTX-90 User Manual

Page 6

Advertising
background image

page 4

Stand-alone application, no current loop used

Transmitter

Terminals

4
3
2
1

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Power Supply
DC 12 - 24 V

Power
Supply
Power
Supply

Connection to a PLC with built-in power supply

PLC

Terminals

Power Supply
Ground
Power
Supply
Loop Input
4-20 mA
Loop Input
4-20 mA

Internal PLC
Connection

Connection to a PLC/Recorder, separate supply

PLC or Recorder

Loop Input
4-20 mA in
Loop Input
4-20 mA in

DC 12 - 24 V

Power
Supply
Power
Supply

Example: Two transmitters connected to PLC/Recorder

with separate power supply

Transmitter 2

4
3
2
1

DC 12 - 24 V

Power
Supply
Power
Supply

Transmitter 1

4
3
2
1

Transmitter

Terminals

4
3
2
1

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Transmitter

Terminals

4
3
2
1

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

PLC or Recorder

Channel 1
4-20 mA in
Channel 1
4-20 mA in

Channel 2
4-20 mA in
Channel 2
4-20 mA in

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

AUX required for all CDTX-90 systems.

System Pwr

Loop -

System Pwr

Loop +

AUX

Power -

AUX

Power +

4

3

2

1

Sensr Gnd

(SHIELD)

Iso. Gnd

(BLACK)

Temp. IN

(WHITE)

Signal IN

(RED)

14

13

12

11

Relay 2

(NO)

Relay 2

(COM)

Relay 2

(NC)

Relay 1

(NO)

Relay 1

(COM)

Relay 1

(NC)

10

9

8

7

6

5

Terminals 5-10: Relay Outputs
• Two SPDT mechanical relays, programmable as:

• High or Low setpoint with adjustable hysteresis.

• proportional Pulse (400 pulses per minute maximum).

• May be disabled (Off) if not used.

Terminals 3 and 4: Loop Power
12-24 VDC ±10% system power
and current loop output.
Max. loop impedance:
50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24 V

Terminals 1-2: Auxiliary power
Provides DC power to sensor.
Required for all CDTX-90 systems.

CDTX-90-2 System Power/Loop Connections

CDTX-90-2 Terminal Connections

Terminals 11-14: Sensor input
11 is conductivity input
12 is temperature input
13 is the isolated signal ground
14 is the sensor earth ground