Appendix A: Troubleshooting

83

The temperature sensor has been

disconnected or has brok

en wires.

1.

The temperature reading is -20

° F

or -30

° C.

Pr

ob

lem

T

emperature Monitoring:

Examine the wires to temperature sensor and

connect or replace wiring.

Tr

y mo

ving the unit to a dif

ferent location.

a)

T

emperature sensing ma

y be af

fected b

y

a source of ambient heat (ie., direct

sunlight, or heat duct pro

ximity).

3.

T

emperature reading is inaccurate.

2.

T

emperature reads 150

° F

or 65

° C.

T

emperature sensor wires are touching or

ha

v

e shor

ted.

V

erify and cor

rect wiring.

b)

T

emperature ma

y require calibration.

After mo

ving or placing the unit a

wa

y from

ambient heat sources, the temperature ma

y

be calibrated to of

fset inaccurate nor

mal

reading b

y

se

v

eral de

g

rees. Refer to Chapter

5, Section 5.6.

Cause

Solution