5-2

Section

Connecting to the Host’s RS-422A/485 Port

104

C1000H/C2000H rack-mounting type: 3G2A5-LK201-EV1

Setting the Front Switches

@ Mode selector (key switch)

Set this to Host link.

Local

Host

Mode

selector

Setting the Rear Switches

I/O port

RS-422A

RS-232C

Synchronization

Internal

External

OFF

ON

CTS

0V

External

@ I/O port selection (selector switch)

Set this to RS-422A.

@ Unit # (DIP SW1)

Set SW1-1 to SW1-5 to OFF (0).

@ Synchronization (selector switch)

Set this to Internal.

@ Communications speed

(DIP SW2-1 to SW2-4)

Set these switches to 0010 to select
19200 bps.

Set these switches to 1010 to select
9600 bps.

(0: OFF 1: ON)

@ 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

@ Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).

(Levels 1, 2, and 3 are enabled.)

@ CTS selection (selector switch)

Set this always to 0V (ON).

Terminator

@ Terminator setting (selector switch)

Set this switch to ON.

ON

ON

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

SW1

SW2