Connecting to the Host’s RS-422A/485 Port

129

Pin Nos. 9 and 10

Function

Shorted

Terminal resistance is applied.

Short only at the NT31/NT31C connected to the end of an
RS-422A/485 cable.

Open

Terminal resistance is not applied.

Leave the terminals open when connecting an NT31/NT31C
anywhere other than at the end of the RS-422A/485 cable.

Note Before connecting or disconnecting cables between devices, make sure that the

power supply to all of the connected devices (NT31/NT31C, PC, etc.) is OFF.

Reference:

S The internal circuit of the NT31/NT31C is shown below.

16 (RDA)

9 (TRM)

10 (RDB)

+

Terminal resistor (120

Ω)

Making a connection here inserts a terminator between
+ (RDB) and

− (RDA).

S For details on setting the terminal resistance of the host unit, refer to setting

methods for each type of the communication.