Omron Programmable Terminals NT31 NT31C User Manual

Page 116

Advertising
background image

5-2

Section

Connecting to the Host’s RS-422A/485 Port

105

C1000H/C2000H rack-mounting type: C500-LK203

Setting the Rear Switches

I/O port

RS-422A

RS-232C

Synchronization

Internal

External

Terminator

OFF

ON

CTS

0V

External

@ I/O port selection (selector switch)

Set this to RS-422A.

@ Synchronization (selector switch)

Set this to Internal.

@ Communications speed

(DIP SW2-1 to SW2-4)

Set these switches to 0010 to select
19,200 bps.

Set these switches to 1010 to select
9,600 bps.

(0: OFF 1: ON)

@ 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

@ Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).

(Levels 1, 2, and 3 are enabled.)

5V supply

ON

OFF

@ Unit #, parity, and transfer code

(DIP SW1-1 to SW1-7)

Set SW1-1 to SW1-7 to OFF (0).

@ CTS selection (selector switch)

Set this always to 0V (ON).

@ Terminator setting (selector switch)

Set this switch to ON.

SW1

SW2

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

ON

ON

C200H/C1000H/C2000H CPU mounting type: 3G2A6-LK202-EV1

Setting the Rear Switches

SW1

SW2

SW3

@ Unit #, parity, and transfer code

(DIP SW1-1 to SW1-5)

Set SW1-1 to SW1-5 to OFF (0).

* Parity is fixed at Even Parity. Transfer code is

fixed at ASCII 7 data bits and 2 stop bits.

@ Communications speed (DIP SW2-1 to SW2-4)

Set these switches to 0010 to select 19,200 bps.

Set these switches to 1010 to select 9,600 bps.

(0: OFF 1: ON)

@ 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

@ Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).

(Levels 1, 2, and 3 are enabled.)

@ Terminator setting (DIP SW3-1 to SW3-6)

Set SW3-1, SW3-3, and SW3-5 to ON (1).

Set SW3-2, SW3-4, and SW3-6 to OFF (0).

(Set terminator ON.)