46-649 Jupiter Magnetostrictive Transmitter - F

OUNDATION

fieldbus™

5.1.3 FF Segment Checklist

There can be several reasons for a F

OUNDATION

fieldbus

installation to be in a faulty condition. In order to assure
that communication can be established, the following
requirements must be met.

• Device supply voltage must be higher than 9 VDC with a

maximum of 32 VDC.

• Total current draw of a given segment cannot exceed the

rating shown on the power conditioner and/or barrier.

• Two 100

Ω, 1 µF terminators must be connected to the

network—one at each end of the segment.

• Cable length plus spur length must not exceed the following

values:

• The cable shield is to be hard grounded only at one point

close to the DCS. In addition, the cable shield can be
capacitively grounded in multiple places to improve EMC
protection.

Number of Spurs

1 Device

2 Devices

3 Devices

4 Devices

25–32

19–24

100 ft. (30 m)

15–18

200 ft. (60 m)

100 ft. (30 m)

13–14

300 ft. (90 m)

200 ft. (60 m)

100 ft. (30 m)

1–12

400 ft. (120 m) 300 ft. (90 m)

200 ft. (60 m)

100 ft. (30 m)

Pair

Shield

Twisted

Size

Length

Type

Single

Yes

Yes

AWG 18 (0.8 mm2)

6,200 ft. (1,900 m)

A

Multi

Yes

Yes

AWG 22 (0.32 mm2)

3,900 ft. (1,200 m)

B

Multi

No

Yes

AWG 26 (0.13 mm2)

1,300 ft. (400 m)

C

Multi

Yes

No

AWG 16 (1.25 mm2)

650 ft. (200 m)

D