Gas piping installation, Warning, Table 1 – Trane YCZ036F1/3M0B User Manual

Page 13: Table 2

Advertising
background image

Page 13

CAUTION: Before making the gas pipe connection give seri-
ous consideration to providing the required clearance neces-
sary to remove the access panels on the unit (e.g., economizer
and filter access panels).

NOTE: In the absence of local codes, the installation must
conform with American National Standard--Z223.1--National
Fuel Gas Code, Latest Revision.

The available gas supply must agree with the required gas supply
marked on the unit nameplate. Minimum permissible gas supply
pressure for purpose of input adjustment must be at least 7.0 in.
w. c. (inches water column) for natural gas and 11 in. w. c. for LP gas.

PIPE DELIVERY SCHEDULE

NOTE: The following procedure and tables below apply to
Natural Gas only.

1. Obtain from the gas company the heating value and specific

gravity of the gas delivered.

2. Determine the exact length of pipe needed.

3. Read BTUH input nameplate on the furnace.

4. Use the multiplier opposite the specific gravity of the gas given

in Table 1 below and insert in the following formula:

CFH =

Furnace Input in BTUH

Gas Heat Content in BTU/Cu. Ft. X Multiplier

TABLE 1

This will give the factor for columns 2 through 6 in Table 2.

GAS PIPING INSTALLATION

7. Read horizontally to the left of this column for the required pipe

size diameter.

5. Using Table 2, select the pipe length nearest to yours.

TABLE 2

6. Follow this line vertically down to the exact CFH found in Step 4

above or the next highest value.

NATURAL GAS ONLY

TABLE OF CUBIC FEET PER HOUR OF GAS

FOR VARIOUS PIPE SIZES AND LENGTHS

PIPE
SIZE

(inch)

LENGTH OF PIPE (feet)

10

20

30

40

50

60

70

1/2

132

92

73

63

56

50

46

3/4

278

190

152

130

115

105

96

1

520

350

285

245

215

195

180

1-1/4

1050

730

590

520

440

400

370

THIS TABLE IS BASED ON PRESSURE DROP OF 0.3 INCH W.C. AND 0.6 SP.GR. GAS

NOTE: If this is an LPG application, consult your LPG supplier
for pipe sizes and deliveries.

GAS PRESSURE SETUP PRECAUTIONS

IMPORTANT: The furnace and its individual shut-off valve
must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures
exceeding 1/2 psig (3.48 kPa).

The furnace must be isolated from the gas supply piping system by
closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures less than
or equal to 1/2 psig (3.48 kPa).

GAS SUPPLY LINE PRESSURE

Before connecting the unit to the gas supply line, be sure to
determine the gas pressure in the line.

If the gas supply pressure is excessive (above 14 inches water
column or 1/2 psig), install a pressure regulator either at the supply
source or in the branch circuit serving the unit. Once the regulator
is installed, set it to provide a pressure of 7 inches water column with
the unit operating and no greater than 14 inches water column with
the unit not firing.

NOTE: Gas pressure in excess of 14 inches water column
(1/2 psig) may damage the regulator, while improper regulation
may result at pressures lower than 5.5 inches water column at
the unit inlet.

If the supply line pressure is below the minimum supply pressure
indicated on the unit nameplate, contact the gas supply company.

Follow these steps to complete the installation of the unit gas piping.
See Figure 14.

1. Install a tapped, Style A (1/8-inch NPT tap) shut-off gas cock at

the end of the gas supply line near the unit. Be sure the tapped
gas cock is downstream of the pressure regulator, if used.

SPECIFIC

GRAVITY

MULTIPIER

MULTIPIERS TO BE USED

WHEN THE SPECIFIC

GRAVITY OF THE GAS IS

OTHER THAN 0.60

.50

1.10

.55

1.04

.60

1.00

.65

.962

DEALER INSTALLED

GROUND UNION

1/8" N.P.T.PLUGGED

ACCESS FOR TEST

GAUGE CONNECTION

FROM

GAS SUPPLY

DRIP LEG

FIELD SUPPLIED MAIN

GAS VALVE, MUST BE

INSTALLED BY DEALER

OUTSIDE UNIT.

UNIT

TO MAIN

CONTROL

VALVE

6"

MIN

SCHEMATIC DIAGRAM OF

GAS PIPING TO UNIT

WARNING:

NEVER USE AN OPEN FLAME

TO TEST FOR GAS LEAKS: AN EXPLOSION COULD
OCCUR, CAUSING INJURY OR DEATH.

r

Advertising
This manual is related to the following products: