INPUT CHECK AND ADJUSTMENT

1. Make sure all gas appliances are off except the furnace.

2. Clock the gas meter with the furnace operating (determine the

dial rating of the meter) for one revolution.

3. Match the “Sec” column in the gas flow (in cfh) Table 3 with the

time clocked.

4. Read the “Flow” column opposite the number of seconds

clocked.

5. Use the following factors if necessary.

For 1 Cu. Ft. Dial Gas Flow CFH =

Chart Flow Reading / 2

For 1/2 Cu Ft. Dial Gas Flow CFH =

Chart Flow Reading / 4

For 5 Cu. Ft. Dial Gas Flow CFH =

10X Chart Flow Reading / 4

6. Multiply the final figure by the heating value of the gas obtained

from the utility company and compare to the nameplate rating.
This must not exceed the nameplate rating.

7. Changes can be made by adjusting the manifold pressure.

a. Attach a manifold pressure gauge.

b. Remove the slot screw on top of the gas valve for 1st stage

manifold pressure adjustment. Remove slot screw on outlet
side for 2nd stage adjustment (See Figure 17).

c. Turn the adjustment nut in to increase the gas flow rate, and

out to decrease the gas flow rate using a 3/32" hex wrench.

Note:

If Model YCZ036F1,3M is installed in a region where NOX must be
below 40 nanograms per input to 72,000 BTUH.

GAS PIPING INSTALLATION

GAS FLOW IN CUBIC FEET PER HOUR

2 CUBIC FOOT DIAL

Sec.

Flow

Sec.

Flow

Sec.

Flow

Sec.

Flow

8

900

29

248

50

144

82

88

9

800

30

240

51

141

84

86

10

720

31

232

52

138

86

84

11

655

32

225

53

136

88

82

12

600

33

218

54

133

90

80

13

555

34

212

55

131

92

78

14

514

35

206

56

129

94

76

15

480

36

200

57

126

96

75

16

450

37

195

58

124

98

73

17

424

38

189

59

122

100

72

18

400

39

185

60

120

104

69

19

379

40

180

62

116

108

67

20

360

41

176

64

112

112

64

21

343

42

172

66

109

116

62

22

327

43

167

68

106

120

60

23

313

44

164

70

103

124

58

24

300

45

160

72

100

128

56

25

288

46

157

74

97

132

54

26

277

47

153

76

95

136

53

27

267

48

150

78

92

140

51

28

257

49

147

80

90

144

50

TABLE 3

u

1st Stage (Lo)

Manifold

Pressure

Adjustment

2nd Stage (Hi)

Manifold

Pressure

Adjustment

HIGH ALTITUDE INSTALLATION

Unit nameplate ratings are based on equipment operation from sea
level to 2000 feet elevation above sea level. If the unit installation
is from 2000 - 4500 feet elevation, it will be necessary to change
the burner orifices to the noted sizes, (ref. National Fuel Gas Code,
sec 8.1.2, Appendix F, Table F4).

S

A

G

E

P

Y

T

S

S

E

R

P

.

N

A

M

)

.

C

.

W

.

n

i

(

E

Z

I

S

E

C

I

F

I

R

O

t

f

0

0

0

2

-

0

E

Z

I

S

E

C

I

F

I

R

O

t

f

0

0

5

4

-

0

0

0

2

L

A

R

U

T

A

N

3

.

3

2

4

*

3

4

E

N

A

P

O

R

P

0

.

0

1

4

5

5

5

*

D

E

P

P

I

H

S

Y

R

O

T

C

A

F

Switch Toggles
"ON" or "OFF"

Advertising
This manual is related to the following products: