Checkout procedure, Troubleshooting chart, Ign led diagnostic indicator – Trane YCZ036F1/3M0B User Manual

Page 21

Advertising
background image

Page 21

TROUBLESHOOTING CHART

SYSTEM

FAULTS

ELECTRICAL

REFRIGERANT CIRCUIT

P-PRIMARY CAUSES S-SECONDARY CAUSES

Liquid Pressure Too high

Liquid Pressure Too Low

Suction Pressure Too High

Suction Pressure Too Low

Liquid Refrigerant floodback (TXV System)

Liquid Refrig. floodback (Cap. Tube System)

I. D. Coil Frosting

Compressor Runs Inadequate or No Cooling

Compressor & O.D. fan Do Not Start

Compressor Will Not Start But O.D. Fan Runs

O.D. Fan Won't Start

Compressor Hums But Will Not Start

Compressor Cycles on IOL

I.D. Blower Won't Start

CHECKOUT PROCEDURE

p

IGN LED DIAGNOSTIC INDICATOR

FLASHING SLOW

NORMAL CALL FOR HEAT

CONTINUOUS ON

NORMAL

CONTINUOUS OFF

CHECK POWER / INTERNAL FAILURE

2 FLASHES

SYSTEM LOCKOUT ( NO FLAME )

3 FLASHES

PRESSURE SWITCH PROBLEM

4 FLASHES

HIGH LIMIT (TCO) OPEN

5 FLASHES

FLAME SENSED WITH GAS VALVE OFF

6 FLASHES

FLAME ROLLOUT SWITCH (FL) OPEN

7 FLASHES

W1 & W2 SWAPPED