Gas piping installation – Trane YCZ036F1/3M0B User Manual

Page 14

Advertising
background image

Page 14

NOTE: The shut-off gas cock must be installed outside of the
unit and should meet the specifications of all applicable national
and local codes
.

2. Install a ground union joint downstream of the shut-off cock.

This joint must also be installed outside of the unit.

3. Install a drip leg at least six (6) inches in depth next to the union

as shown in Figure 14. This drip leg is required to collect any
sediment that may be deposited in the line.

4. Before connecting the piping circuit to the unit, bleed the air

from the supply line. Then cap or plug the line and test the
pressure at the tapped shut-off cock. The pressure reading
should not exceed 14 inches water column.

5. Using an appropriate backup wrench on the gas valve inlet

boss, connect the gas piping to the unit. Check the completed
piping for leaks using a soap and water solution or the equiva-
lent.

6. After installation of the gas pipe in the unit, the pipe chase

opening should be closed with the filler/barrier plug provided.

MANIFOLD PRESSURE

Check the manifold pressure at the unit gas valve. Do not exceed
the recommended pressure shown on the unit nameplate.

GAS PIPING INSTALLATION

BURNER & VALVE ILLUSTRATION

FLUE AND HOOD ILLUSTRATION

y

t

C664399

MANIFOLD

COVER

2ND STAGE
ADJUSTMENT
3/32" ALLEN

BRACKET-BURNER
HOLD DOWN

BURNER

ORFICE

SCREW

1ST STAGE
ADJUSTMENT
3/32" ALLEN

SCREW

BRACKET
BURNER
SUPPORT

C664400

GAS VALVE

ALTERNATE
MANUAL
"ON/OFF"
SWITCH

FUSE LINK

Advertising
This manual is related to the following products: