Connection information, Connection sizes, Names and functions – Toshiba DEV001Z User Manual

Page 5

Advertising
background image

E6581268

- 4 -

2. Connection Information

2.1. Connection

Sizes

Connection Instance

Produced

Consumed

I/O Messaging

4 or 8 bytes

4 or 8 bytes

Explicit Messaging

49 bytes

49 bytes

Notes
- For the Explicit Messaging connection, this is the maximum message length: shorter messages are also acceptable.
- For the Polled I/O connection, if the actual consumed data size is less than the connection instance’s

consumed_connection_size attribute, the consumed data will be ignored, but the connection will otherwise produce
normally. If the actual consumed data size is larger than the connection instance’s consumed_connection_size attribute,
the consumed data will be ignored and the connection will not produce.

2.2. Names and functions

The external view of this option and the name of each part are shown below:

SW1: Terminal F, R

SINK/SOURCE switching

MS (Module status) LED

(Refer to 2.3)

Common serial communication connector

DeviceNet connector

NS (Network status) LED

(Refer to 2.3)

SW2: Factory set up

* Please do not change this switch from the factory

shipments. It becomes the cause of failure.

F

R

VIA CC P24

G/E FLA FLB FLC

RJ45