Frequently asked questions – TC electronic SDN BHD D22 User Manual

Page 29

Advertising
background image

27

FREQUENTLY ASKED QUESTIONS

Question: What parameters can be set using serial remote
control of the D22?
Answer: Preset change, Delay time and Bypass using an
RS485/422/232 controller.

Question: What serial protocol is used?
Answer: The serial protocol is 9600, N, 8, 1.
This means 9.6 kbaud, no parity, 8 bit, 1 stop.

Question: What is the command structure for the remote
protocol?
Answer: #AA,CMD,VALUE<CR>

AA is Unit Address number as set on the Utility page.
CMD is command:
PRE for preset change,
BYP for Bypass,
DEL for delay.
VALUE is (RAM) Preset number, 0 for Not Bypass, 1 for
Bypass or amount of Delay.
<CR> is carriage return, the same as Enter or hex 0D.

Examples:
#05,PRE,10<CR> =Recall RAM preset no. 10 on D22 address 5.
#03,BYP,1<CR> =Bypass D22 address 3.

All commands and numbers are shown as ASCII.

Question: What is the data length of the delay time?
Answer: The delay is always a decimal number related to the
given delay unit of the D22. It is not posible to change delay unit
via the RS-485, so you must set this manually before you send
the command lines.

Example 1:
The delay unit is ms and you would like to set the delay to 10.5 ms:
#05,DEL,10.5<CR>

Example 2:
The delay unit is frames and you would like to set the delay to
10.5 frames: #05,DEL,10.5<CR>

As you can see there is no difference between example 1 and 2.

Example 3: The delay unit is ms and you would like to set the

delay to 10.5 frames:
You have to calculate the delay in ms yourself based on the fps
setting and then send a command-line.

Question: What ASCII characters should be sent for Recall of
RAM preset no. 10 on D22 address 5?
Answer: #05,PRE,10<CR> means these values (hex) actually
transmitted 23 30 35 2C 50 52 45 2C 31 30 0D

Advertising