General theory of operation – Technicolor - Thomson TS 870 User Manual

Page 12

Advertising
background image

TS 870 TRANSFER SWITCH

PM062 REV 5 08/05/05

8

Thomson Technology

4.2.

TYPICAL COMMISSIONING PROCEDURES

CAUTION:

Commissioning procedures must be performed by qualified

personnel only. Ensure the Automatic Transfer Switch

(ATS) Control Circuit Isolation Plug is disconnected prior to

energizing the supply sources. Manually place the transfer

switch mechanism in the neutral position prior to applying

power. Failure to do so may result in equipment failure or

personal injury.

Note:

The

TYPICAL

AUTOMATIC

TRANSFER

SWITCH

COMMISSIONING

PROCEDURES MODEL SERIES TS 870 (attached as “Appendix A ”) is provided for

general information only pertaining to typical site installations and applications. Contact

Thomson Technology for further information as may be required.

Note: An optional hand held, plug-in Service Display Module (SDM) is available for the TSC

80 Transfer Controller. The SDM module provides an LCD screen to display additional

detailed information on the operation and settings of the TSC 80 controller for simplified

servicing/trouble shooting procedures. For detailed information, refer to the separate SDM

module instruction manual (PM065).

5.

GENERAL THEORY OF OPERATION

5.1.

STANDARD AUTOMATIC TRANSFER SWITCH

5.1.1. NORMAL OPERATION

When utility supply voltage drops below a preset nominal value (adjustable from 70%

to 100% of nominal) on any phase, an engine start delay circuit is initiated and the

transfer to utility supply signal will be removed (i.e. contact opening). Following

expiry of the engine start delay period (adjustable from 0 to 60 sec.) an engine start

signal (contact closure) will be given.

Once the engine starts, the transfer switch controller will monitor the generator

voltage and frequency levels. Once the generator voltage and frequency rises above

preset values (adjustable from 70% to 95% of nominal), the engine warm-up timer

Advertising