TS 870 TRANSFER SWITCH

PM062 REV 5 08/05/05

13

Thomson Technology

5. Attach a safety lockout padlock to the service disconnect control switch to

prevent unauthorized change in operating condition and verify transfer switch

door is locked closed.

6. To reenergize the load, remove the padlock(s) from the service

disconnect control switch, and move the switch to the Energized position.

The transfer switch will immediately return to the utility or generator supply if

within normal operating limits.

5.3.

TEST MODES

The transfer switch may be tested utilizing the TSC 80 controller push-buttons or optional

four position test switch. A simulated utility power failure condition will be activated when the

test mode is selected. The transfer switch will operate as per a normal utility power fail

condition.

The transfer switch will remain on generator supply until the test mode is terminated. It will

then immediately transfer back to the utility supply and then continue to operate the

generator set for its cooldown period then stop.

Note: The transfer switch will automatically

return to the utility supply (if within nominal limits) if the generator set fails while in the test

mode.

6.

OVER CURRENT PROTECTION

Thomson Technology TS 870 series of Automatic Transfer Switches may be supplied with or

without integral over current protection as described below:

6.1.

STANDARD TS 870 AUTOMATIC TRANSFER SWITCH

The standard TS 870 Automatic Transfer Switch does not contain any integral over current

protection and requires upstream over current protection devices for both Utility and

Generator sources. The Standard TS 870 is rated for 100% continuous loading and can

withstand a maximum short circuit fault current as noted in

Section 15

of this manual. The

standard TS 870 transfer switch model without integral over current protection is identified in

the product model code. Refer to

Section 4.1

of this manual for further details on model

coding

.

6.2.

OPTIONAL TS 870 AUTOMATIC TRANSFER SWITCH WITH INTEGRAL
OVER CURRENT PROTECTION

TS 870 transfer switches will have integral over current protection supplied on the Utility

source as standard. The type of over current protection utilized is dependent upon ATS

amperage size and optional features specified. For transfer switches rated 100A through