Technicolor - Thomson TS 870 User Manual

Page 6

Advertising
background image

TS 870 TRANSFER SWITCH

PM062 REV 5 08/05/05

2

Thomson Technology

ventilated area free of corrosive agents including fumes, salt and concrete/cement

dust. Apply heat as necessary to prevent condensation.

2.1.2.

EQUIPMENT OPERATING

The transfer switch shall be operated in an environment with a temperature range not

exceeding +5° to +122° Fahrenheit (-15° to +50° Celsius) and a humidity range not

exceeding 5%-95% non-condensing.

3.

NOTES TO INSTALLER

DANGER!!!!

Arc Flash and Shock Hazard. Will cause severe injury or death.

Do not open equipment until ALL power sources are disconnected

This equipment must be installed and serviced only by qualified electrical

personnel utilizing safe work practices and appropriate Personal Protective

Equipment (PPE). Failure to do so may cause personal injury or death

3.1.

UPSTREAM CIRCUIT PROTECTIVE DEVICES/ELECTRICAL
CONNECTIONS

To ensure satisfactory installation of this equipment be sure to observe "Cable Terminal

Information” regarding power cable connection tightness and "Requirements for Upstream

Circuit Protective Devices" located in this manual.

All mechanical and electrical connections must be checked for tightness prior to placing this

equipment in service to ensure proper operation and to validate applicable warranty

coverage.

Advertising