10. RECOMMENDED MAINTENANCE

DANGER!!!!

Arc Flash and Shock Hazard. Will cause severe injury or death.

Do not open equipment until ALL power sources are disconnected

This equipment must be installed and serviced only by qualified electrical

personnel utilizing safe work practices and appropriate Personal Protective

Equipment (PPE). Failure to do so may cause personal injury or death

10.1. DO NOT perform dielectric tests on the equipment with the control components in the

circuit.

10.2. Check if control components are tight in sockets.

10.3. Periodically inspect all terminals (load, line and control) for tightness. Re-torque all

bolts, nuts and other hardware. Clean or replace any contact surfaces, which are

dirty, corroded or pitted.

10.4. Transfer switches should be in a clean, dry and moderately warm location. If signs of

moisture are present, dry and clean transfer switch. If there is corrosion, try to clean

it off. If cleaning is unsuitable, replace the corroded parts. Should dust and/or debris

gather on the transfer switch, brush, vacuum, or wipe clean. DO NOT blow dirt into

power switching devices.

10.5. Test the transfer switch operation. While the unit is exercising, check for freedom of

movement, hidden dirt, corrosion or any excessive wear on the mechanical operating

parts. Ensure that the power switching device travel is correct.

10.6. Verify all program settings on the TSC 80 controller as per the TSC 80 component

calibration label on the rear cover of the controller.

10.7. Transfer Mechanism 1000A-1200A-T Style ensure that the manual handle moves

freely on the hub when the lock pin is disengaged. If lubrication is necessary, apply

medium weight (SAE 20) oil sparingly.

10.8. Transfer Mechanism 1000A-1200A T Style -yoke pivot bearings and rod ends are

permanently lubricated and do not require maintenance.

10.9. Transfer Mechanism 100A-800A S Style –lubrication of drive hub/operator arm

interface. Use high viscosity moly lubricant.