Technicolor - Thomson TS 870 User Manual

Page 19

Advertising
background image

TS 870 TRANSFER SWITCH

PM062 REV 5 08/05/05

15

Thomson Technology

7.

GENERAL NOTES ON SERVICING TRANSFER SWITCH
MECHANISM

DANGER!!!!

Arc Flash and Shock Hazard. Will cause severe injury or death.

Do not open equipment until ALL power sources are disconnected

This equipment must be installed and serviced only by qualified electrical

personnel utilizing safe work practices and appropriate Personal Protective

Equipment (PPE). Failure to do so may cause personal injury or death


Note
: Refer to product drawings in sections 12, 13 & 14 for identification of Transfer Switch
Mechanism style supplied with the Transfer Switch.

When performing any service work on the transfer mechanism, it is imperative that the following be

observed:

7.1.

To maintain mechanical integrity, ensure that:

On T Style mechanisms, all limit switches are correctly adjusted to provide full

travel of the power switching device toggles without exerting unnecessary forces

associated with excessive travel. Ensure that power switching device travel far

enough to reset any internal trip unit (it is more important for the toggle to go fully

in the "off" direction, than in the "on" direction).

Mechanical interlocking is correct when one power switching opens well before

the other should close.

All fasteners are adequately tightened.

The operating linkages are not damaged or bent, and that all bearing points

operate freely.

On S style transfer switch mechanisms, check nylock nuts on bolt pivot points.

Operation arms should move freely without excessive play.

7.2.

To maintain electrical integrity, ensure that:

All electrical connections, especially power connections, are clean and

adequately tightened. Corroded or loose power connections will cause

destructive heating, and may cause premature tripping.

All insulating devices are in place and in good condition.

Advertising