BE1-87G - General Information

1-5

SPECIFICATIONS

BE1-87G relays are available in single-phase and three-phase configurations, and with the following features
and capabilities.

Current Sensing Inputs

(5 Ampere)

Nominally rated at 5 amperes, with a range of 45 to 65 hertz. Maximum
current per input: 10 amperes continuous, 250 amperes for 1 second.

(1 Ampere)

Nominally rated at 1 ampere, with a range of 45 to 65 hertz. Maximum
current per input: 2 amperes continuous, 50 amperes for 1 second.

Current Sensing Burden

(5 Ampere)

Burden is less than 0.05 ohms per input.

(1 Ampere)

Burden is less than 0.25 ohms per input.

Stabilizing Reactor

Refer to Section 4 for stabilizing reactor impedance characteristic curves.

I

2

t Rating

(5 Ampere)

65 amperes for 1 second at 70

(

C ambient, (I

2

t = 4225).

(1 Ampere)

13 amperes for 1 second at 70

(

C ambient, (I

2

t = 4225).

Pickup Control

A front panel control permits minimum differential (operate) currents to be
selected. This sensitivity is constant for restraint currents less than the
nominal current (5 or 1 amperes). Actual operating characteristics are
shown in graph format in Section 5,

Testing And Setting

the relay.

(5 Ampere)

Minimum differential (operate) current = 0.1, 0.15, 0.2, 0.4, 0.5, 0.8, or 1.6
amperes. The ideal operating characteristic is approximated by the
following equations.

where

I

R

is the restraint current, defined as the lesser of the input currents.

I

OP

is the operate current

I

S

is the front panel setting

For I

R



5 amperes: I

OP

= I

S

For I

R

> 5 amperes: I

OP

= I

S

+ 0.5(I

R

- 5)

(1 Ampere)

Minimum differential (operate) current = 0.02, 0.03, 0.04, 0.08, 0.10, 0.16,
or 0.32 ampere. The ideal operating characteristic is approximated by the
following equations.

For I

R



1 ampere: I

OP

= I

S

For I

R

> 1 ampere: I

OP

= I

S

+ 0.5(I

R

- 1)

Pickup Accuracy

(5 Ampere)

For I

R



5 amperes, ±5% of the operate pickup characteristic or 25

milliamperes whichever is greater. Actual operating characteristics are
shown in graph format in Section 5,

Testing And Setting

the relay.

For I

R



5 amperes, up to a maximum of 20 amperes, ±8% of the operate

pickup characteristic or 150 milliamperes, whichever is greater. Actual
operating characteristics for pickup values between 5 and 20 amperes are
shown in graph format in Section 5,

Testing And Setting

the relay.