TRENDnet BE1-87G User Manual

Page 18

Advertising
background image

BE1-87B - Installation

4-1

Figure 4-1. S1 Case, Outline Dimensions, Front View

SECTION 4 • INSTALLATION

GENERAL

When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to prevent
damage during transit. Immediately upon receipt of a relay, check the model and style number against the
requisition and packing list to see that they agree. Visually inspect the relay for damage that may have occurred
during shipment. If there is evidence of damage, immediately file a claim with the carrier and notify the Regional
Sales Office, or contact the Sales Representative at Basler Electric, Highland, Illinois.

In the event the relay is not to be installed immediately, store the relay in its original shipping carton in a moisture
and dust free environment. When relay is to be placed in service, it is recommended that the operational test
procedure in Section 5,

Testing And Setting

, be performed prior to installation.

DIELECTRIC TEST

In accordance with IEC 255-5 and ANSI/IEEE C37.90-1989, one-minute dielectric (high potential) tests may be
performed as follows:

All circuits to ground:

2828 Vdc

Input to output circuits:

2000 Vac or 2828 Vdc

MOUNTING

Relay

Because the relay is of solid state design, it
does not have to be mounted vertically. Any
convenient mounting angle may be chosen.
Relay outline dimensions and panel drilling
diagrams are shown in Figures 4-1 through 4-
7. Numbers in parentheses indicate metric
dimensions (millimeters). All other dimensions
are in inches.