1-7

Isolation

In accordance with ANSI/IEEE C37.90, one minute dielectric (high
potential) tests as follows:

All circuits to ground:

2121 Vdc

Input to output circuits:

1500 Vac or 2121 Vdc

Surge Withstand Capability

Qualified to ANSI/IEEE C37.90.1-1989

Standard Surge Withstand

Capability (SWC) Tests for Protective Relays and Relay Systems

.

Fast Transient

Qualified to ANSI/IEEE C37.90.1-1989.

Impulse Test

Qualified to IEC 255-5.

Radio Frequency

Maintains proper operation when tested for interference in accordance

Interference (RFI)

with IEEE C37.90.2, Trial-Use Standard Withstand Capability of Relay
systems to Radiated Electromagnetic Interference from Transceivers.

Temperature

Operating Range
-40

(

C (-40

(

F) to 70

(

C (158

(

F)

Recommended Storage Range
-65

(

C (-85

(

F) to 100

(

C (212

(

F).

Shock

15 g in each of three mutually perpendicular planes.

Vibration

2 g in each of three mutually perpendicular planes swept over the range
of 10 to 500 hertz for a total of six sweeps, 15 minutes each sweep.

Weight

3-phase: 19.2 pounds maximum.
1-phase: 14.3 pounds maximum.

Case Size

All units are supplied in an S1 size case.