General data – Trane CGWF User Manual

Page 14

Advertising
background image

CG-PRC012-EN

14

Table GD-1. General data — CGWF water-cooled chiller

Size

20

25

30

40

50

60

Compressor

Quantity (1)

2

2

2

2/2

2/2

2/2

Nominal Size (tons) (2)

10/10

10/15

15/15

10-10/10-10

10-15/10-15

15-15/15-15

Steps of Unloading (%)

100,50

100,60

100,50

100,75,50,25

100,80,60,30

100,75,50,25

Evaporator

Water Storage

(gallons)

12

11

16

13

21

40

(liters)

45

42

61

49

80

151

Min. Flow

(gpm)

24

30

36

48

60

84

(L/s)

1.5

1.9

2.3

3.0

3.8

4.7

Max. Flow

(gpm)

72

90

108

144

180

252

(L/s)

4.5

5.7

6.8

9.1

11.4

17.3

Condenser

Water Storage

(gallons)

5.0

6.1

7.6

11.7

13.9

14.0

(liters)

18.9

23.2

28.9

44.2

52.7

53.1

Min. Flow

(gpm)

30

36

50

60

72

90

(L/s)

1.9

2.3

3.2

3.8

4.5

5.7

Max. Flow

(gpm)

90

108

146

180

216

325

(L/s)

5.7

6.8

9.2

11.4

13.6

20.5

General Unit

Refrigerant

R-22

R-22

R-22

R-22

R-22

R-22

No. of Independent
Refrigerant Circuits

1

1

1

2

2

2

Refrigerant

(pound)

50

50

90

50/50

50/50

75/75

Charge

(kilogram)

22.7

22.7

40.8

22.7/22.7

22.7/22.7

34/34

Oil Charge

(pints)

16

22

28

16/16

22/22

28/28

(liters)

7.6

10.4

13.2

7.6/7.6

10.4/10.4

13.3/13.3

Notes
1. Data containing information on two circuits shown as follows: CKT 1/CKT 2
2. Nominal compressor sizes based on 60 Hz.

Table GD-2. General data — CCAF compressor chiller

Size

20

25

30

40

50

60

Compressor

Quantity (1)

2

2

2

2/2

2/2

2/2

Nominal Size (tons) (2)

10/10

10/15

15/15

10-10/10-10

10-15/10-15

15-15/15-15

Steps of Unloading (%)

100,50

100,60

100,50

100,75,50,25

100,80,60,30

100,75,50,25

Evaporator

Water Storage

(gallons)

12

11

16

13

21

19

(liters)

45

42

61

49

80

72

Min. Flow

(gpm)

24

30

36

48

60

84

(L/s)

1.5

1.9

2.3

3.0

3.8

4.7

Max. Flow

(gpm)

72

90

108

144

180

252

(L/s)

4.5

5.7

6.8

9.1

11.4

17.3

General Unit

Refrigerant

R-22

R-22

R-22

R-22

R-22

R-22

No. of Independent
Refrigerant Circuits

1

1

1

2

2

2

Refrigerant

(pound)

6

8

12

6/6

8/8

12/12

Charge

(kilogram)

2.7

3.6

5.4

2.7/2.7

3.6/3.6

5.5/5.5

Oil Charge

(pints)

16

22

28

16/16

22/22

28/28

(liters)

7.6

10.4

13.2

7.6/7.6

10.4/10.4

13.3/13.3