Part load performance performance data – Trane CGWF User Manual

Page 23

Advertising
background image

23

CG-PRC012-EN

Table PD-5. Part-load performance for CGWF 20-60 ton – 60 Hz in English units

Unit Size

100%

IPLV

Tons

19.9

20

kW

15.2

20.3

EER

15.5

Tons

24.5

25

kW

19.0

20.5

EER

15.4

Tons

29.2

30

kW

22.8

20.3

EER

15.3

Tons

39.4

40

kW

30.1

20.7

EER

15.6

Tons

48.6

50

kW

37.6

19.6

EER

15.4

Tons

59.4

60

kW

46.5

19.8

EER

15.2

Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. EER and IPLV values include compressor and control kW.
3. kW input is for compressors only.

Table PD-6. Part-load performance for CGWF 20-60 ton – 50 Hz in English units

Unit Size

100%

IPLV

Tons

16.7

20

kW

12.4

21.0

EER

16.1

Tons

20.6

25

kW

15.5

20.9

EER

16.0

Tons

24.5

30

kW

18.5

20.7

EER

15.9

Tons

33.0

40

kW

24.5

21.3

EER

16.2

Tons

40.8

50

kW

30.6

20.3

EER

16.0

Tons

50.1

60

kW

37.6

20.4

EER

16.0

Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. EER and IPLV values include compressor and control kW.
3. kW input is for compressors only.

Part Load
Performance

Performance
Data